JZP Transformer inotungamira pasi rose mukushandira chikamu chesimba rinodzokororwa pasi rose. Neruzivo rwakaratidzwa, takapa zviuru zvematransformer emapurojekiti ekuchengetedza simba remagetsi muNorth America, Europe, neAustralia. Zvigadzirwa zvedu hazvingosviki chete pamatanho akaomarara akadai seIEEE, ANSI, CSA, AN, IEC, uye BS, asiwo zvine zvitupa zvinosanganisira UL, cUL, CSA, CE, SGS, nezvimwe, zvichitsigirwa nemishumo yakazara yekuyedza.
Kushanda zvakanaka, kuvimbika, uye kuchengetedzeka ndizvo zvinhu zvikuru zvatinotevedzera tisingazununguki.
Zvinodiwa zveSG250HX Transformer
1) Transformer inofanira kunge yakakodzera kushanda ne pulsed inverter.
2) Kana mushonga wekudzivirira PID (ungangove wakakonzera kukuvadzwa) ukashandiswa, mawindings echipiri etransformer anofanira kukwanisa kubata Vrms=906V VAC peak voltage reference pasi ye1500V system. Rutivi rweLV rwetransformer uye voltage yepamusoro-soro yemidziyo yekudzivirira mheni yeLV yetransformer inofanira kutevedzera zvinodiwa izvi.
3) Voltage inobuda yeSG250HX i800Vac LL (640~920Vac), 50Hz kana 60Hz. Voltage iri kudivi reMV inofanira kuenderana nevoltage yeMV grid panzvimbo yekubatanidza, transformer ine tap changer ndiyo inonyanya kufarirwa.
4) Kugona kwetransformer kunofanira kuenderana nesimba guru reInverters rinobuda
5) Transformer inopatsanurwa kaviri (mbiri yeLV, imwe yeMV side) inofanira kushandiswa, mawinding maviri eLV anodiwa.
Kubatanidza Dy11y11 kunogona kushandiswa. Transformer inomonereka kaviri (imwe yeLV, imwe yeMV side) inofanira kushandiswa, kumonereka kamwe chete kweLV kunodiwa, uye kunobatanidza Dy11 kunogona kushandiswa.
6) Voltage yeImpedance Z(%) inofanira kutevedzera zvinodiwa zvakajairwa. Zvakadai seIEC 60076 kana IEEE C57.12.34 uye C57.12.00.
7) Transformer inofanira kukwanisa kutsungirira mwero wakati we harmonic current, huwandu hwepamusoro hwe harmonic current i5% ye fundamental current pa nominal power.
8) Transformer inofanira kutsungirira mwero wakati weDC component, 0.5% ye fundamental current pa nominal power.
9) Transformer inofanira kutsungirira kusawirirana kwechikamu, 5% yemagetsi pamagetsi emagetsi.
10) Kutenderedzwa kweLV kweMV transformer kunofanira kutsungirira voltage gradient dU/dt inosvika 500V/μs pasi.
11) Dziviriro yakanaka uye kupatsanurwa pakati pemawindings eLV neMV.
12) Transformer inofanira kunge yakagadzikwa panzvimbo imwe chete, uye pasi pe transformer inofanira kunge yakachengeteka.
13) Kirasi yekudzivirira kupisa inofanira kunge iri F kana kupfuura Transformer yerudzi rwakaomas naA zverudzi rwemafuta.
Kirasi yekudzivirira AEBFHNC
Kupisa kwakanyanya (℃) 105 120 130 155 180 200 220
Kukwidzwa kwetemperature yekumonera (K) 60 75 80 100 125 135 150
14) Kushanda zvakanaka kwemutoro kunofanira kuenderana nezvinodiwa zvemuno.
15) Nzvimbo yemuno (tembiricha, hunyoro, kureba, mhepo, nezvimwewo) inofanira kufungwa nezvayo.
16) Kukwira kwetembiricha uye kudzima kwemagetsi kunofanira kutariswa kunyanya kana kukwirira kuri pamusoro pe1000m.
17) Kuwanda kwegrid nenyika yakatarwa uye zviyero zvinofanirwa kuremekedzwa.