+86 18068001229 01
Transformer ine 2000kVA ine Pad nhatu
Tsananguro yeChigadzirwa
Matransformer eJZP Transformer e2000kVA, 34.5kV akaiswa pad-mounted ari muBattery Energy Storage System (BESS) muKern County, California, uko anopa simba rekubatsira rakavimbika rekutsigira michina yakasiyana-siyana iri muchiteshi chekuchengetera simba. Akapedzwa muna Chivabvu 2024 uye akaendeswa kuvatengi vekuAmerica, matransformer aya akakosha pakuona kuti kushanda kwawo hakuchinji uye kutarisirwa kwakanaka kwekuchengetwa kwesimba.
01020304050607
| Kupisa kwemhepo | Minimum -15.0°C, Maximum 41.0°C, avhareji yepamusoro yemaawa makumi maviri nemana 33.0°C |
| Kukwirira | |
| Mamiriro ekudengenyeka kwenyika: | Chikamu cheNjodzi: II, Kirasi yeSaiti D |
| SS = 1.28 g, S1 = 0.43 g, SMS = 1.54 g, SM1 = 1.09 g, SDS = 1.03 g, SD1 = 0.73 g |
| Kushanda kwemazita (chikamu-ku-chikamu) | 34.5kV |
| Kushanda kwakanyanya (chikamu kusvika chikamu) | 38kV |
| Kugadzika kwekumonera | Delta |
| Chiyero cheBushing | 600A |
| Kudzivirira kutenderedza | 200kV BIL |
| Kudzivirira mabhazi | 200kV BIL |
| Huwandu hweBushing | Nhanhatu (Loop Feed) |
| Kutsungirira kwedunhu pfupi | 30kA |
| Bvisa kubatana | LBOR Switch |
| Bvisa huwandu hweswitch | Chikamu chimwe (1) chezvikamu zvitatu |
| Kushanda kwemazita (chikamu-ku-chikamu) | 480V |
| Kugadzika kwekumonera | Wye yakagayiwa |
| Kudzivirira kutenderedza uye kuputira matanda BIL | MOTA YE30KV |
| Kutsungirira kwenguva pfupi | 65 kA* |
| LV bushing spade hole quaty | (8) HAPANA maburi maviri |
| Chinhu chinogara chichikwira simba | 110% |
| Kuramba kwakasimba | Aihwa |
| Bhazi repasi | Ehe |
| Kudzora voltage yemagetsi edunhu | 277V AC |
| Tsanangudzo yemuchina wekupwanya dunhu | UL yakanyorwa |
| Yakakodzera kupinda musevhisi | Ehe |
| Chiyero (mukati) | H*D*H: 83.9*94.7*95.3 |
| Tangi & Zvishongedzo | 4,630lbs |
| Oiri yehuwandu | 900Gal |
| Huremu Hwose | 21,600lbs |
Zvinhu Zvikuru & Mabhenefiti
Kugovera Simba Zvinoshanda Kwekuchengetedza Simba
Matransformer e2000kVA akagadzirwa kuti adzike kubva paMedium Voltage (MV) kuenda kuLow Voltage (LV), zvichiita kuti akwanise kubatanidzwa nema switchboards mumasisitimu ekuchengetera simba. Kugadziriswa uku kwe stepdown kwakakosha pakuona kuti simba rinogoverwa zvakanaka uye rakavimbika kumidziyo yekubatsira, zvichitsigira kushanda zvakanaka kweBESS infrastructure.
Kutonhodza Kunogara Kwenguva Refu Uye Kunodhura Mari Yakawanda
Zvichienderana nekuzvipira kweJZP Transformer kukuchengetedza nguva, matransformer anoshandisa mafuta anoora semvura inotonhorera. Iyi mhinduro isingakuvadzi nharaunda haingopi chete hunhu hwakanaka hwekudzivirira kupisa asiwo inotsigira kushandiswa kwesimba.
Kugara Nekuchengetedzeka Kwakavakirwa Mukati
NEMA 3R Enclosures: Matransformer edu akaiswa muNEMA 3R-rated electrical enclosures asingapindi mvura, asingapindi chando, uye asingapindi sinou, ane nzira dzekubvisa mvura dzakavakirwa mukati. Maenclosure aya anopa dziviriro yakasimba kubva kumamiriro ekunze, achichengetedza zvikamu zvemagetsi zvemukati uye achivimbisa kugara kwenguva refu kunyangwe mumamiriro ekunze akaoma.
Zvinhu Zvinodzivirira Kukanganisika Uye Kuchengetedza: Zvakagadzirwa nepfungwa dzekuchengetedza, ma transformer ane nzira dzakasiyana dzekukiya nekusunga kudzivirira kupinda nekukanganisika kusina mvumo, zvichideredza njodzi yekubiwa uye kuona kuti kushanda kwakachengeteka nguva dzese.
Dhizaini Yakanaka Mushandisi Yekuchengetedza & Kushanda Zvakanaka
Rutivi rwe transformer rune simba shoma rine dhizaini yakasarudzika yakasungirirwa padivi ine huro kuti zvive nyore kubatanidza ne switchboard. Mageji akaiswa kunze, mavharuvhu emuenzaniso, uye masisitimu ekudhonza mvura zviri mu kabhineti inokiyiwa ine lock yebhoti ine mapoinzi mashanu. Dhizaini iyi yakasiyana inobvumira vashandisi kuongorora mazinga emafuta zvakachengeteka, kuyedza mageji, uye kuita mabasa ekugadzirisa vasina kuzvipinza mumabushings ane simba guru (HV) kana low-voltage (LV), zvichiwedzera zvakanyanya kuchengetedzeka uye kushanda zvakanaka.

Mageji ekunze e transformer akaiswa pad
Kutarisa Kwepamusoro & Zviziviso Zviri Kure
Kuti ive nechokwadi chekuti inoshanda zvakanaka nguva dzose, transformer ine zviratidzo zvemazinga emafuta uye tembiricha zvine nzvimbo mbiri dzekutarisa dziri kure. Zviratidzo izvi zvinopa data renguva chaiyo kune vanoshanda, zvichitumira zviratidzo zvekunyevera kana huwandu hwemafuta hwakakwira zvakanyanya kana kuti hwakaderera zvakanyanya. Pamusoro pezvo, kana tembiricha yemvura inotonhodza ikadarika 85°C, sisitimu ichatanga alarm. Kana tembiricha ikakwira kupfuura 105°C, transformer ichazvibvisa otomatiki kubva pagrid kudzivirira kupisa zvakanyanya uye kukuvara kunogona kuitika, zvichiita kuti sisitimu ive yakachengeteka uye yakavimbika.

Hunhu & Kutevedzera Mutemo
MaJZP Transformers anogadzirwa zvichienderana nezvinodiwa neindasitiri, zvinosanganisira UL, ANSI, IEEE, uye NEMA, zvichiita kuti zvive nyore kushanda, kuvimbika, uye kuchengetedzeka. Kuzvipira kwedu kune mhando uye hunyanzvi kunovimbisa kuti transformer yega yega yakavakwa zvinoenderana nezvinodiwa zvepamusoro, ichipa sevhisi yakavimbika muhupenyu hwese hwemuchina.

Bvunza Izvozvi! (or) Bvunza Izvozvi!
Kana muine mibvunzo nezvezvigadzirwa zvedu kana runyorwa rwemitengo, ndapota titumirei email yenyu uye tichakutaurirai mukati memaawa makumi maviri nemana.